系统工程与电子技术 ›› 2021, Vol. 43 ›› Issue (8): 2174-2180.doi: 10.12305/j.issn.1001-506X.2021.08.19

• 系统工程 • 上一篇    下一篇

基于性能的复杂装备现场可更换单元规划

杨刚, 吴旭升, 孙盼*, 朱浩, 熊胜   

  1. 海军工程大学电气工程学院, 湖北 武汉 430033
  • 收稿日期:2020-08-15 出版日期:2021-08-01 发布日期:2021-08-05
  • 通讯作者: 孙盼
  • 作者简介:杨刚(1992—), 男, 助教, 硕士研究生, 主要研究方向为装备测试性|吴旭升(1976—), 男, 教授, 博士研究生导师, 博士, 主要研究方向为装备测试性、无线电能传输|孙盼(1986—), 男, 助理研究员, 博士研究生, 主要研究方向为装备测试性、无线电能传输|朱浩(1985—), 男,博士研究生,主要研究方向为电机故障诊断|熊胜(1991—), 男,硕士研究生,主要研究方向为装备测试性
  • 基金资助:
    湖北省自然科学基金创新群体项目(2018CFA008);国家自然科学基金青年科学基金(52007195)

Partition of line replaceable units in complex equipment based on performance

Gang YANG, Xusheng WU, Pan SUN*, Hao ZHU, Sheng XIONG   

  1. College of Electrical Engineering, Naval University of Engineering, Wuhan 430033, China
  • Received:2020-08-15 Online:2021-08-01 Published:2021-08-05
  • Contact: Pan SUN

摘要:

针对复杂装备设计研制阶段的现场可更换单元(line replaceable unit, LRU)规划问题, 以功能-行为-结构(function behavior structure, FBS)和可靠性、维修性、保障性、测试性(reliability maintainability supportability testability, RMST)作为LRU规划的影响因素, 提出了一种基于性能的LRU规划方法。首先, 通过建立系统的功能架构, 获取系统的零部件清单。在此基础上, 建立零部件FBS相关关系评价矩阵, 进而得到零部件综合相关矩阵, 运用模糊聚类分析实现初步的LRU规划。将RMST参量化, 建立综合评价数学模型, 对初步规划方案进行优选, 得到最佳规划方案。最后, 以某型中压整流发电机为例, 运用提出的方法实现了该装备的LRU规划, 验证了方法的有效性。

关键词: 现场可更换单元规划, 模糊聚类, 复杂装备, 中压整流发电机

Abstract:

Aiming at the partition of line replaceable units (LRU) in design development stage of complex equipment, a LRU partition method based on performance is proposed, which function behavior structure (FBS) and reliability maintainability supportability testability (RMST) are used as the influencing factors in this method. Firstly, the list of spare parts of system is obtained by establishing functional architecture. On this basis, the evaluation matrixes for correlation of components in FBS are established, and then a comprehensive correlation matrix of components is obtained, and the preliminary partition of LRU is finished through fuzzy cluster analysis. The comprehensive evaluation mathematical model by quantifying RMST is established to sequence the preliminary partition schemes for obtaining the optimal partition scheme. Finally, taking a certain type of medium-voltage rectifier generator as an example, the proposed method is used for LRU partition of the equipment, and the effectiveness of the method is verified.

Key words: line replaceable units (LRU) partition, fuzzy clustering, complex equipment, medium voltage rectifier generator

中图分类号: